IEC LV, XLPE Insulation, ATA, PVC 0.6/1 kV

Products

1x120

Nexans ref. 21120BXZVEB09BD0

  • Packaging: Drum (m)
  • Conductor cross-section: 120 mm²
  • Approximate weight: 1320 kg/km
  • Nominal outer diameter: 22.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Permissible current rating in open air: 400 A
  • Permissible current rating when buried: 257 A
  • Voltage drop, single phase: 0.39 V/A.km

 

1x150

Nexans ref. 21150BXZVEB09BD0

  • Packaging: Drum (m)
  • Conductor cross-section: 150 mm²
  • Approximate weight: 1620 kg/km
  • Nominal outer diameter: 24.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Permissible current rating in open air: 464 A
  • Permissible current rating when buried: 287 A
  • Voltage drop, single phase: 0.34 V/A.km

 

1x185

Nexans ref. 21185BXZVEB09BD0

  • Packaging: Drum (m)
  • Conductor cross-section: 185 mm²
  • Approximate weight: 1970 kg/km
  • Nominal outer diameter: 26.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
  • Permissible current rating in open air: 533 A
  • Permissible current rating when buried: 324 A
  • Voltage drop, single phase: 0.29 V/A.km

 

1x240

Nexans ref. 21240BXZVEB09BD0

  • Packaging: Drum (m)
  • Conductor cross-section: 240 mm²
  • Approximate weight: 2480 kg/km
  • Nominal outer diameter: 28.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
  • Permissible current rating in open air: 634 A
  • Permissible current rating when buried: 375 A
  • Voltage drop, single phase: 0.25 V/A.km

 

1x300

Nexans ref. 21300BXZVEB09BD0

  • Packaging: Drum (m)
  • Conductor cross-section: 300 mm²
  • Approximate weight: 3050 kg/km
  • Nominal outer diameter: 31.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
  • Permissible current rating in open air: 736 A
  • Permissible current rating when buried: 419 A
  • Voltage drop, single phase: 0.22 V/A.km

 

1x400

Nexans ref. 21400BXZVEB09BD0

  • Packaging: Drum (m)
  • Conductor cross-section: 400 mm²
  • Approximate weight: 3870 kg/km
  • Nominal outer diameter: 35.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
  • Permissible current rating in open air: 868 A
  • Permissible current rating when buried: 717 A
  • Voltage drop, single phase: 0.19 V/A.km

 

1x50

Nexans ref. 21050BXZVEB09BD0

  • Packaging: Drum (m)
  • Conductor cross-section: 50 mm²
  • Approximate weight: 610 kg/km
  • Nominal outer diameter: 16.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Permissible current rating in open air: 216 A
  • Permissible current rating when buried: 153 A
  • Voltage drop, single phase: 0.84 V/A.km

 

1x500

Nexans ref. 21500BXZVEB09BD0

  • Packaging: Drum (m)
  • Conductor cross-section: 500 mm²
  • Approximate weight: 4950 kg/km
  • Nominal outer diameter: 39.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0366 Ohm/km
  • Permissible current rating in open air: 998 A
  • Permissible current rating when buried: 791 A
  • Voltage drop, single phase: 0.17 V/A.km

 

1x630

Nexans ref. 21630BXZVEB09BD0

  • Packaging: Drum (m)
  • Conductor cross-section: 630 mm²
  • Approximate weight: 6175 kg/km
  • Nominal outer diameter: 43.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0283 Ohm/km
  • Permissible current rating in open air: 1151 A
  • Permissible current rating when buried: 861 A
  • Voltage drop, single phase: 0.16 V/A.km

 

1x70

Nexans ref. 21070BXZVEB09BD0

  • Packaging: Drum (m)
  • Conductor cross-section: 70 mm²
  • Approximate weight: 820 kg/km
  • Nominal outer diameter: 18.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Permissible current rating in open air: 278 A
  • Permissible current rating when buried: 188 A
  • Voltage drop, single phase: 0.61 V/A.km

 

1x800

Nexans ref. 21800BXZVEB09BD0

  • Packaging: Drum (m)
  • Conductor cross-section: 800 mm²
  • Approximate weight: 7790 kg/km
  • Nominal outer diameter: 48.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0221 Ohm/km
  • Permissible current rating in open air: 1246 A
  • Permissible current rating when buried: 904 A
  • Voltage drop, single phase: 0.15 V/A.km

 

1x95

Nexans ref. 21095BXZVEB09BD0

  • Packaging: Drum (m)
  • Conductor cross-section: 95 mm²
  • Approximate weight: 1080 kg/km
  • Nominal outer diameter: 20.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Permissible current rating in open air: 342 A
  • Permissible current rating when buried: 226 A
  • Voltage drop, single phase: 0.47 V/A.km

 

Description

Description

Standards

  • International
    IEC 60332-1; IEC 60502-1

Application


These power cables are used for electricity supply in low voltage installation systems.

They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant…)

 

Design

 

  1. Conductor
    Stranded bare copper class 2 acc. to IEC 60228
     
  2. Insulation
    Cross Linked Polyethylene "XLPE"
     
  3. Inner Sheath or Bedding
    Lapped bedding or extruded PVC
     
  4. Armour
    Aluminium Tape Armour "ATA"
  1. Outer Sheath 
    Polyvinyl Chloride "PVC"

      Options:

 

       - Flame retardant, Option "CAT A, CAT B, CAT C" to IEC60332 or equivalent.

       - Ozone resistant.

       - Oil resistant.

       - Anti termite.

 Installation Conditions:

  1. Air Temperature : 30 Deg.
  2. Ground Temperature: 20 Deg.
  3. Soil Thermal Resistivity : 2.5 k.m/w
  4. Depth of lay : 0.7 m

 All dimensions have tolerance +- 7 %

Marking

no. of cores x conductor sizes mm2 Cu / XLPE / ATA / PVC 600/1000 V   IEC 60502-1  MADE IN QATAR QICC-Nexans Year Meters

Custom marking available

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Insulation
XLPE (Cross-linked Polyethylene)
Inner sheath
PVC
Armour type
Aluminium tape
Outer sheath
PVC
Colour
Black
Conductor flexibility
Stranded class 2
Halogen free
No

Dimensional characteristics

Dimensional characteristics

Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
15 (xD)
Bending factor when installed
8 (xD)

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close