5x2.5
5x2.5
Galvanized steel wire armoured LV cable, PVC sheathed for fixed installations. Rated voltage 0.6/1 KV
Read more- Nexans ref. : 25003FXZVSB99BS0
Description
Description
Standards
-
ProductADWEA-LV-UAE; BS 5467
-
TestIEC 60332-3 Cat.A
Application
These power cables are used for electricity supply in low voltage installation systems.
They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant…)
This family is fully compling with ADWEA specifications from UAE.
Design
- Conductor
Stranded bare copper class 2 acc. to BS 6360 and IEC 60228
- Insulation
Cross Linked Polyethylene "XLPE"
- Inner Sheath or Bedding
Extruded PVC
- Armour
Galvanized Steel Wire Armour "SWA"
- Outer Sheath
Polyvinyl Chloride "PVC", Flame retardant to BS 4066 CAT A or equivalent, Oil and Sulphide resistance
Installation Conditions:
- Air Temperature : 30 Deg.
- Ground Temperature: 20 Deg.
- Soil Thermal Resistivity : 2.5 k.m/w
- Depth of lay : 0.7 m
All dimensions have tolerance +- 7 %
Marking
no. of cores x conductor sizes mm2 Cu / XLPE / SWA / PVC 600/1000 V BS 5467 BASEC MADE IN QATAR QICC-Nexans Year Meters
Custom marking available
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Conductor shape
Circular
Insulation
XLPE (chemical)
Inner sheath
PVC
Armour type
Galvanized steel wires
Outer sheath
PVC
Colour
Black
Conductor flexibility
Stranded class 2
Halogen free
No
Dimensional characteristics
Dimensional characteristics
Number of cores
5
Conductor cross-section
2.5 mm²
Approximate weight
460 kg/km
Ground conductor cross-section
- mm²
Nominal outer diameter
16.0 mm
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
0,6/1 kV
Max. DC resistance of the conductor at 20°C
7.41 Ohm/km
Permissible current rating in open air
33 A
Permissible current rating when buried
30 A
Voltage drop, 3 conductors
14.0 V/A.km
Usage characteristics
Usage characteristics
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
15 (xD)
Bending factor when installed
8 (xD)