ALSECURE® IEC LV, XLPE Insulation, SWA, HFFR 0.6/1 kV

Products

10x1.5

Nexans ref. 2D002BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 10
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 900 kg/km
  • Nominal outer diameter: 20.0 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

10x2.5

Nexans ref. 2D003BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 10
  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 1110 kg/km
  • Nominal outer diameter: 22.0 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

12x1.5

Nexans ref. 2E002BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 12
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 710 kg/km
  • Nominal outer diameter: 19.0 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

12x2.5

Nexans ref. 2E003BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 12
  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 890 kg/km
  • Nominal outer diameter: 21.0 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

19x1.5

Nexans ref. 2F002BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 19
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 930 kg/km
  • Nominal outer diameter: 22.0 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

19x2.5

Nexans ref. 2F003BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 19
  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 1300 kg/km
  • Nominal outer diameter: 25.0 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

24x1.5

Nexans ref. 2I002BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 24
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 1250 kg/km
  • Nominal outer diameter: 25.0 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

24x2.5

Nexans ref. 2I003BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 24
  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 1590 kg/km
  • Nominal outer diameter: 28.0 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

2x1.5

Nexans ref. 22002BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 300 kg/km
  • Nominal outer diameter: 13.0 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

2x10

Nexans ref. 22010BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 10 mm²
  • Approximate weight: 700 kg/km
  • Nominal outer diameter: 18.0 mm
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
  • Permissible current rating in open air: 78 A
  • Permissible current rating when buried: 65 A
  • Voltage drop, 3 conductors: 3.5 V/A.km

 

2x120

Nexans ref. 22120BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 120 mm²
  • Approximate weight: 3460 kg/km
  • Nominal outer diameter: 36.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Permissible current rating in open air: 353 A
  • Permissible current rating when buried: 257 A
  • Voltage drop, 3 conductors: 0.37 V/A.km

 

2x150

Nexans ref. 22150BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 150 mm²
  • Approximate weight: 4110 kg/km
  • Nominal outer diameter: 39.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Permissible current rating in open air: 406 A
  • Permissible current rating when buried: 287 A
  • Voltage drop, 3 conductors: 0.3 V/A.km

 

2x16

Nexans ref. 22016BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 16 mm²
  • Approximate weight: 1045 kg/km
  • Nominal outer diameter: 21.0 mm
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating in open air: 99 A
  • Permissible current rating when buried: 84 A
  • Voltage drop, 3 conductors: 2.2 V/A.km

 

2x185

Nexans ref. 22185BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 185 mm²
  • Approximate weight: 5330 kg/km
  • Nominal outer diameter: 44.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
  • Permissible current rating in open air: 463 A
  • Permissible current rating when buried: 324 A
  • Voltage drop, 3 conductors: 0.26 V/A.km

 

2x2.5

Nexans ref. 22003BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 380 kg/km
  • Nominal outer diameter: 14.0 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

2x25

Nexans ref. 22025BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 25 mm²
  • Approximate weight: 1080 kg/km
  • Nominal outer diameter: 21.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Permissible current rating in open air: 131 A
  • Permissible current rating when buried: 107 A
  • Voltage drop, 3 conductors: 1.65 V/A.km

 

2x35

Nexans ref. 22035BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 35 mm²
  • Approximate weight: 1510 kg/km
  • Nominal outer diameter: 24.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Permissible current rating in open air: 162 A
  • Permissible current rating when buried: 129 A
  • Voltage drop, 3 conductors: 1.15 V/A.km

 

2x4

Nexans ref. 22004BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 4 mm²
  • Approximate weight: 450 kg/km
  • Nominal outer diameter: 15.0 mm
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Permissible current rating in open air: 44 A
  • Permissible current rating when buried: 39 A
  • Voltage drop, 3 conductors: 8.7 V/A.km

 

2x50

Nexans ref. 22050BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 50 mm²
  • Approximate weight: 1900 kg/km
  • Nominal outer diameter: 26.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Permissible current rating in open air: 197 A
  • Permissible current rating when buried: 153 A
  • Voltage drop, 3 conductors: 0.89 V/A.km

 

2x6

Nexans ref. 22006BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 6 mm²
  • Approximate weight: 540 kg/km
  • Nominal outer diameter: 16.0 mm
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 56 A
  • Permissible current rating when buried: 49 A
  • Voltage drop, 3 conductors: 5.9 V/A.km

 

2x70

Nexans ref. 22070BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 70 mm²
  • Approximate weight: 2130 kg/km
  • Nominal outer diameter: 29.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Permissible current rating in open air: 251 A
  • Permissible current rating when buried: 188 A
  • Voltage drop, 3 conductors: 0.6 V/A.km

 

2x95

Nexans ref. 22095BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 2
  • Conductor cross-section: 95 mm²
  • Approximate weight: 2890 kg/km
  • Nominal outer diameter: 33.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Permissible current rating in open air: 304 A
  • Permissible current rating when buried: 226 A
  • Voltage drop, 3 conductors: 0.45 V/A.km

 

37x1.5

Nexans ref. 2M002BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 37
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 1610 kg/km
  • Nominal outer diameter: 28.0 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

37x2.5

Nexans ref. 2M003BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 37
  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 2555 kg/km
  • Nominal outer diameter: 32.0 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

3x1.5

Nexans ref. 23002BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 3
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 330 kg/km
  • Nominal outer diameter: 13.0 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

3x10

Nexans ref. 23010BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 3
  • Conductor cross-section: 10 mm²
  • Approximate weight: 930 kg/km
  • Nominal outer diameter: 20.0 mm
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
  • Permissible current rating in open air: 78 A
  • Permissible current rating when buried: 65 A
  • Voltage drop, 3 conductors: 3.5 V/A.km

 

3x120

Nexans ref. 23120BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 3
  • Conductor cross-section: 120 mm²
  • Approximate weight: 4760 kg/km
  • Nominal outer diameter: 41.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Permissible current rating in open air: 353 A
  • Permissible current rating when buried: 257 A
  • Voltage drop, 3 conductors: 0.37 V/A.km

 

3x150

Nexans ref. 23150BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 3
  • Conductor cross-section: 150 mm²
  • Approximate weight: 6070 kg/km
  • Nominal outer diameter: 46.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Permissible current rating in open air: 406 A
  • Permissible current rating when buried: 287 A
  • Voltage drop, 3 conductors: 0.3 V/A.km

 

3x16

Nexans ref. 23016BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 3
  • Conductor cross-section: 16 mm²
  • Approximate weight: 1240 kg/km
  • Nominal outer diameter: 22.0 mm
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating in open air: 99 A
  • Permissible current rating when buried: 84 A
  • Voltage drop, 3 conductors: 2.2 V/A.km

 

3x185

Nexans ref. 23185BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 3
  • Conductor cross-section: 185 mm²
  • Approximate weight: 7310 kg/km
  • Nominal outer diameter: 50.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
  • Permissible current rating in open air: 463 A
  • Permissible current rating when buried: 324 A
  • Voltage drop, 3 conductors: 0.26 V/A.km

 

3x2.5

Nexans ref. 23003BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 3
  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 410 kg/km
  • Nominal outer diameter: 15.0 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

3x240

Nexans ref. 23240BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 3
  • Conductor cross-section: 240 mm²
  • Approximate weight: 9135 kg/km
  • Nominal outer diameter: 55.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
  • Permissible current rating in open air: 546 A
  • Permissible current rating when buried: 375 A
  • Voltage drop, 3 conductors: 0.21 V/A.km

 

3x25

Nexans ref. 23025BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 3
  • Conductor cross-section: 25 mm²
  • Approximate weight: 1640 kg/km
  • Nominal outer diameter: 24.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Permissible current rating in open air: 131 A
  • Permissible current rating when buried: 107 A
  • Voltage drop, 3 conductors: 1.65 V/A.km

 

3x300

Nexans ref. 23300BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 3
  • Conductor cross-section: 300 mm²
  • Approximate weight: 11015 kg/km
  • Nominal outer diameter: 60.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
  • Permissible current rating in open air: 628 A
  • Permissible current rating when buried: 419 A
  • Voltage drop, 3 conductors: 0.18 V/A.km

 

3x35

Nexans ref. 23035BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 3
  • Conductor cross-section: 35 mm²
  • Approximate weight: 2030 kg/km
  • Nominal outer diameter: 27.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Permissible current rating in open air: 162 A
  • Permissible current rating when buried: 129 A
  • Voltage drop, 3 conductors: 1.15 V/A.km

 

3x4

Nexans ref. 23004BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 3
  • Conductor cross-section: 4 mm²
  • Approximate weight: 510 kg/km
  • Nominal outer diameter: 16.0 mm
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Permissible current rating in open air: 44 A
  • Permissible current rating when buried: 39 A
  • Voltage drop, 3 conductors: 8.7 V/A.km

 

3x400

Nexans ref. 23400BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 3
  • Conductor cross-section: 400 mm²
  • Approximate weight: 13760 kg/km
  • Nominal outer diameter: 67.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
  • Permissible current rating in open air: 731 A
  • Permissible current rating when buried: 439 A
  • Voltage drop, 3 conductors: 0.17 V/A.km

 

3x50

Nexans ref. 23050BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 3
  • Conductor cross-section: 50 mm²
  • Approximate weight: 2520 kg/km
  • Nominal outer diameter: 30.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Permissible current rating in open air: 197 A
  • Permissible current rating when buried: 153 A
  • Voltage drop, 3 conductors: 0.89 V/A.km

 

3x6

Nexans ref. 23006BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 3
  • Conductor cross-section: 6 mm²
  • Approximate weight: 610 kg/km
  • Nominal outer diameter: 17.0 mm
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 56 A
  • Permissible current rating when buried: 49 A
  • Voltage drop, 3 conductors: 5.9 V/A.km

 

3x70

Nexans ref. 23070BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 3
  • Conductor cross-section: 70 mm²
  • Approximate weight: 2860 kg/km
  • Nominal outer diameter: 33.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Permissible current rating in open air: 251 A
  • Permissible current rating when buried: 188 A
  • Voltage drop, 3 conductors: 0.6 V/A.km

 

3x95

Nexans ref. 23095BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 3
  • Conductor cross-section: 95 mm²
  • Approximate weight: 3940 kg/km
  • Nominal outer diameter: 38.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Permissible current rating in open air: 304 A
  • Permissible current rating when buried: 226 A
  • Voltage drop, 3 conductors: 0.45 V/A.km

 

4x1.5

Nexans ref. 24002BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 4
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 370 kg/km
  • Nominal outer diameter: 14.0 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

4x10

Nexans ref. 24010BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 4
  • Conductor cross-section: 10 mm²
  • Approximate weight: 1100 kg/km
  • Nominal outer diameter: 21.0 mm
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
  • Permissible current rating in open air: 78 A
  • Permissible current rating when buried: 65 A
  • Voltage drop, 3 conductors: 3.5 V/A.km

 

4x120

Nexans ref. 24120BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 4
  • Conductor cross-section: 120 mm²
  • Approximate weight: 6450 kg/km
  • Nominal outer diameter: 47.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
  • Permissible current rating in open air: 353 A
  • Permissible current rating when buried: 257 A
  • Voltage drop, 3 conductors: 0.37 V/A.km

 

4x150

Nexans ref. 24150BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 4
  • Conductor cross-section: 150 mm²
  • Approximate weight: 7645 kg/km
  • Nominal outer diameter: 51.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
  • Permissible current rating in open air: 406 A
  • Permissible current rating when buried: 287 A
  • Voltage drop, 3 conductors: 0.3 V/A.km

 

4x16

Nexans ref. 24016BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 4
  • Conductor cross-section: 16 mm²
  • Approximate weight: 1430 kg/km
  • Nominal outer diameter: 24.0 mm
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating in open air: 99 A
  • Permissible current rating when buried: 84 A
  • Voltage drop, 3 conductors: 2.2 V/A.km

 

4x185

Nexans ref. 24185BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 4
  • Conductor cross-section: 185 mm²
  • Approximate weight: 9250 kg/km
  • Nominal outer diameter: 56.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0991 Ohm/km
  • Permissible current rating in open air: 463 A
  • Permissible current rating when buried: 324 A
  • Voltage drop, 3 conductors: 0.26 V/A.km

 

4x2.5

Nexans ref. 24003BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 4
  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 470 kg/km
  • Nominal outer diameter: 16.0 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

4x240

Nexans ref. 24240BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 4
  • Conductor cross-section: 240 mm²
  • Approximate weight: 11680 kg/km
  • Nominal outer diameter: 62.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0754 Ohm/km
  • Permissible current rating in open air: 546 A
  • Permissible current rating when buried: 375 A
  • Voltage drop, 3 conductors: 0.21 V/A.km

 

4x25

Nexans ref. 24025BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 4
  • Conductor cross-section: 25 mm²
  • Approximate weight: 1970 kg/km
  • Nominal outer diameter: 27.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Permissible current rating in open air: 131 A
  • Permissible current rating when buried: 107 A
  • Voltage drop, 3 conductors: 1.65 V/A.km

 

4x300

Nexans ref. 24300BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 4
  • Conductor cross-section: 300 mm²
  • Approximate weight: 14140 kg/km
  • Nominal outer diameter: 67.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
  • Permissible current rating in open air: 628 A
  • Permissible current rating when buried: 419 A
  • Voltage drop, 3 conductors: 0.18 V/A.km

 

4x35

Nexans ref. 24035BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 4
  • Conductor cross-section: 35 mm²
  • Approximate weight: 2470 kg/km
  • Nominal outer diameter: 29.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Permissible current rating in open air: 162 A
  • Permissible current rating when buried: 129 A
  • Voltage drop, 3 conductors: 1.15 V/A.km

 

4x4

Nexans ref. 24004BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 4
  • Conductor cross-section: 4 mm²
  • Approximate weight: 580 kg/km
  • Nominal outer diameter: 17.0 mm
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Permissible current rating in open air: 44 A
  • Permissible current rating when buried: 39 A
  • Voltage drop, 3 conductors: 8.7 V/A.km

 

4x400

Nexans ref. 24400BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 4
  • Conductor cross-section: 400 mm²
  • Approximate weight: 18510 kg/km
  • Nominal outer diameter: 77.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
  • Permissible current rating in open air: 731 A
  • Permissible current rating when buried: 439 A
  • Voltage drop, 3 conductors: 0.17 V/A.km

 

4x50

Nexans ref. 24050BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 4
  • Conductor cross-section: 50 mm²
  • Approximate weight: 3150 kg/km
  • Nominal outer diameter: 33.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Permissible current rating in open air: 197 A
  • Permissible current rating when buried: 153 A
  • Voltage drop, 3 conductors: 0.89 V/A.km

 

4x6

Nexans ref. 24006BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 4
  • Conductor cross-section: 6 mm²
  • Approximate weight: 820 kg/km
  • Nominal outer diameter: 19.0 mm
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 56 A
  • Permissible current rating when buried: 49 A
  • Voltage drop, 3 conductors: 5.9 V/A.km

 

4x70

Nexans ref. 24070BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 4
  • Conductor cross-section: 70 mm²
  • Approximate weight: 3890 kg/km
  • Nominal outer diameter: 38.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Permissible current rating in open air: 251 A
  • Permissible current rating when buried: 188 A
  • Voltage drop, 3 conductors: 0.6 V/A.km

 

4x95

Nexans ref. 24095BXZHSB30BD0

  • Conductor shape: Sector-shaped
  • Number of cores: 4
  • Conductor cross-section: 95 mm²
  • Approximate weight: 4930 kg/km
  • Nominal outer diameter: 42.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
  • Permissible current rating in open air: 304 A
  • Permissible current rating when buried: 226 A
  • Voltage drop, 3 conductors: 0.45 V/A.km

 

5x1.5

Nexans ref. 25002BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 5
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 430 kg/km
  • Nominal outer diameter: 15.0 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

5x10

Nexans ref. 25010BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 5
  • Conductor cross-section: 10 mm²
  • Approximate weight: 1270 kg/km
  • Nominal outer diameter: 23.0 mm
  • Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
  • Permissible current rating in open air: 78 A
  • Permissible current rating when buried: 65 A
  • Voltage drop, 3 conductors: 3.5 V/A.km

 

5x16

Nexans ref. 25016BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 5
  • Conductor cross-section: 16 mm²
  • Approximate weight: 1900 kg/km
  • Nominal outer diameter: 27.0 mm
  • Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
  • Permissible current rating in open air: 99 A
  • Permissible current rating when buried: 84 A
  • Voltage drop, 3 conductors: 2.2 V/A.km

 

5x2.5

Nexans ref. 25003BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 5
  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 533 kg/km
  • Nominal outer diameter: 17.0 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

5x25

Nexans ref. 25025BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 5
  • Conductor cross-section: 25 mm²
  • Approximate weight: 2550 kg/km
  • Nominal outer diameter: 31.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
  • Permissible current rating in open air: 131 A
  • Permissible current rating when buried: 107 A
  • Voltage drop, 3 conductors: 1.65 V/A.km

 

5x35

Nexans ref. 25035BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 5
  • Conductor cross-section: 35 mm²
  • Approximate weight: 3170 kg/km
  • Nominal outer diameter: 34.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
  • Permissible current rating in open air: 162 A
  • Permissible current rating when buried: 129 A
  • Voltage drop, 3 conductors: 1.15 V/A.km

 

5x4

Nexans ref. 25004BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 5
  • Conductor cross-section: 4 mm²
  • Approximate weight: 680 kg/km
  • Nominal outer diameter: 18.0 mm
  • Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
  • Permissible current rating in open air: 44 A
  • Permissible current rating when buried: 39 A
  • Voltage drop, 3 conductors: 8.7 V/A.km

 

5x50

Nexans ref. 25050BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 5
  • Conductor cross-section: 50 mm²
  • Approximate weight: 4390 kg/km
  • Nominal outer diameter: 39.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
  • Permissible current rating in open air: 197 A
  • Permissible current rating when buried: 153 A
  • Voltage drop, 3 conductors: 0.89 V/A.km

 

5x6

Nexans ref. 25006BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 5
  • Conductor cross-section: 6 mm²
  • Approximate weight: 950 kg/km
  • Nominal outer diameter: 20.0 mm
  • Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
  • Permissible current rating in open air: 56 A
  • Permissible current rating when buried: 49 A
  • Voltage drop, 3 conductors: 5.9 V/A.km

 

5x70

Nexans ref. 25070BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 5
  • Conductor cross-section: 70 mm²
  • Approximate weight: 4980 kg/km
  • Nominal outer diameter: 44.0 mm
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
  • Permissible current rating in open air: 251 A
  • Permissible current rating when buried: 188 A
  • Voltage drop, 3 conductors: 0.6 V/A.km

 

6x1.5

Nexans ref. 2B002BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 6
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 595 kg/km
  • Nominal outer diameter: 17.0 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

6x2.5

Nexans ref. 2B003BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 6
  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 845 kg/km
  • Nominal outer diameter: 19.0 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

7x1.5

Nexans ref. 2C002BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 7
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 440 kg/km
  • Nominal outer diameter: 16.0 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

7x2.5

Nexans ref. 2C003BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 7
  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 650 kg/km
  • Nominal outer diameter: 19.0 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

9x1.5

Nexans ref. 2K002BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 9
  • Conductor cross-section: 1.5 mm²
  • Approximate weight: 630 kg/km
  • Nominal outer diameter: 18.0 mm
  • Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
  • Permissible current rating in open air: 25 A
  • Permissible current rating when buried: 23 A
  • Voltage drop, 3 conductors: 22.8 V/A.km

 

9x2.5

Nexans ref. 2K003BXZHSB30BD0

  • Conductor shape: Circular
  • Number of cores: 9
  • Conductor cross-section: 2.5 mm²
  • Approximate weight: 770 kg/km
  • Nominal outer diameter: 20.0 mm
  • Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
  • Permissible current rating in open air: 33 A
  • Permissible current rating when buried: 30 A
  • Voltage drop, 3 conductors: 14.0 V/A.km

 

Description

Description

Standards

  • International
    IEC 60332-1; IEC 60502-1

Application


These power cables are used for electricity supply in low voltage installation systems.

They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant…)

 

Design

 

  1. Conductor
    Stranded bare copper class 2 acc. to IEC 60228
     
  2. Insulation
    Cross Linked Polyethylene "XLPE"
     
  3. Inner Sheath or Bedding
    Lapped bedding or extruded HFFR
     
  4. Armour
    Galvanized Steel Wire Armour "SWA"
  1. Outer Sheath 
    Halogen Free Flame retardant "HFFR".

      Options :

             - Flame retardant : "CAT A, CAT B, CAT C" to IEC60332 or equivalent.

             - Ozone resistant.

             - Oil resistant.

             - Anti termite.

 

 Installation Conditions:

  1. Air Temperature : 30 Deg.
  2. Ground Temperature: 20 Deg.
  3. Soil Thermal Resistivity : 2.5 k.m/w
  4. Depth of lay : 0.7 m

 All dimensions have tolerance +- 7 %

Marking

no. of cores x conductor sizes mm2 Cu / XLPE / SWA / HFFR 600/1000 V IEC 60502-1 MADE IN QATAR QICC-Nexans Year Meters

Custom marking available

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Insulation
XLPE (Cross-linked Polyethylene)
Inner sheath
Halogen free flame retardant
Armour type
Galvanized steel wires
Outer sheath
HFFR (Halogene Free Flame Retardant)
Colour
Black
Halogen free
Yes
Conductor flexibility
Stranded class 2

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
8 (xD)
Bending factor when installed
15 (xD)
Smoke density
IEC 61034
Gases corrosivity
IEC 60754-2

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close